Permit: T11CM00043

Parcel: 136125140


Addresses:

9540 E WATSON DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/02/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/24/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1 grounding electrode too small to be #6
2 nipple from meter to panel to be bonded
3 nipple from panel to sub panel to be bonded
4wires to be right size according to print
5 j box on roof to be in upright position & connector loose
6 strut to be deep strut