Permit: T11CM00021

Parcel: 136127020


Addresses:

9821 E DOMENIC LN

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/10/2011 BUILDING - FINAL Approved IVRS - Inspection :*
08/01/2011 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LB AT PANEL MISSING BUSHING AND LOOSE
2) LABEL BREAKER AT PANEL TO BE CLEAR FROM SOLAR PANELS
3) BREAKER BLANK MISSING METAL STRAPS ON GEC MISSING
4) LB AT METER LOOSE CONNECTOR
5) SCREW ON J-BOX ON ROOF WILL NOT TIGHTEN COVER
6) STRUT BRACKET LOOSE AND SILICON OR TAR MISSING