Permit: T11CM00018

Parcel: 116190510


Addresses:

340 N MAIN AV


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T11CM00018

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
09/17/2012 FRAMING Approved IVRS - Inspection :*
03/20/2012 FRAMING Partial Approval IVRS - Inspection :*
1) CLARIFY WEEP WITH ARCHITECT
03/13/2012 FRAMING Denied 1) FIRE BLOCKING REQUIRED AT ALL DROPPED CEILINGS.
2) ALL ELECTRICAL OUTLETS & J-BOXES MUST BE ACCESSIBLE (DON'T HIDE IN CEILING.
3) NO OPENINGS ARE ALLOWED INTO ELECTRICAL BOXES. IMPROPER USE OF MC CLAMPS ON ROMEX HAS LEFT HOLES
4) SECURE ROMEX WITHIN 12" OF OUTLETS.
5) DO NOT PUSH ROMEX AGAINST SHEATHING WHEN YOU INSULATE
6) WINDOWS HAVE NOT BEEN PROPERLY FLASHED
7) MISSING WEEP SCREED
8) SEAL ALL EXTERIOR FOAM PENETRATIONS WITH CAULK
9) PROVIDE MEANS OF REMOVING AIR HANDLER. IT MAY BE A LARGE ACCESS PANEL.