Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2011 | BUILDING - FINAL | Approved | PER INSPECTION PRINT OUT | |
| 04/22/2011 | BUILDING - FINAL | Partial Approval | OK TO RELOCATE EXIT SIGN FROM ABOVE DOUBLE LEAF GLAZED DOORS AT EAST OF ASSEMBLY ROOM. MOVE EXIT SIGN TO INDICATE EXIT TO CORRIDOR, AND POST "THIS IS NOT AN EXIT ON FRONT OF DOOR LEAFS. | |
| 04/19/2011 | BUILDING - FINAL | Partial Approval | 1) NO DOOR ON AN EGRESS PATH MAY REQUIRE A KEY OR ANY SPECIAL KNOWLEDGE FOR EGRESS PURPOSES. 2) NO DOOR REQUIRING PANIC HARDWARE MAY HAVE ANY DEADBOLTS OR OTHE LOCKING DEVICE THAT IS NOT INTERLOCKED WITH THE PANIC RELEASE. 3) PLUMBING FIXTURES TO BE IN GOOD WORKING ORDER. 4) EGRESS CONTROLLED DOORS MUST MEET ALL REQUIREMENTS TO IBC 1008. 5) ALL WORK TO BE COMPLETED |
|
| 04/08/2011 | BUILDING - FINAL | Partial Approval | NEED TO PROVIDE SMOKE DETECTORS IN DUCTS OF MECHANICAL EQUIPMENT. | |
| 03/30/2011 | BUILDING - FINAL | Not ready for Inspection | RECALL ABOVE CEILING AND FINALS ON SAME DAY. PLEASE HAVE AIR-BALANCE REPORT @ FINAL |