Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/22/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MC TO BE STRAPPED 1' FROM BOX 2) LIGHT WHIPS TO BE OFF TEE BAR CEILING 3) OUTLET MUD RING TO BE NOT MORE THAN 1/8 GAP AROUND IT AND NOT TO BE 1/4 BACK FROM SHEETROCK 4) EXIT LIGHT BOX TO BE FLUSH WITH SHEETROCK |
|
| 03/16/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |