Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T11BU01627
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2012 | FIRE SPKLR - FINAL | Approved | ||
04/19/2012 | FIRE SPKLR - FINAL | Partial Approval | 1. all mechanical closets need sprinkler heads under shelves above water heater. 2. Insulate all pipe on stairwells less than 2" accept drains. 3. Need cages on heads in outside stair wells. 4. remove cap on head in hvac closet in club room. 5. room 1106 head in north bedroom to close to light in closet. 6. room 1103 taped head south bedroom. 7. room 1101 capped head in mechanical room. 8. stair 2 level one need cage on head near north exit. 9. room 1310 gap around head in closet south bedroom. 10. 1308 room was locked. 11. head taped in hallway by room 1405. 12. gap around head mechanical room 1506 |