Permit: T11BU01627

Parcel: 117044890


Addresses:

550 N 5TH AV 01


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T11BU01627

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/22/2012 FIRE SPKLR - FINAL Approved
04/19/2012 FIRE SPKLR - FINAL Partial Approval 1. all mechanical closets need sprinkler heads under shelves above water heater.
2. Insulate all pipe on stairwells less than 2" accept drains.
3. Need cages on heads in outside stair wells.
4. remove cap on head in hvac closet in club room.
5. room 1106 head in north bedroom to close to light in closet.
6. room 1103 taped head south bedroom.
7. room 1101 capped head in mechanical room.
8. stair 2 level one need cage on head near north exit.
9. room 1310 gap around head in closet south bedroom.
10. 1308 room was locked.
11. head taped in hallway by room 1405.
12. gap around head mechanical room 1506