Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T11BU01627
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2012 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
04/25/2012 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. ALL DEFICIENCES CORRECTED IN BUILDING 1. 2. STILL WAITING TO SEE ABOUT SPRINKLERS IN MECH CLOSETS. |
|
04/04/2012 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. pump test complete. 2. still need to see and test monitoring and alarm to pump. |
|
01/10/2012 | FIRE SPKLR - OH PIPING & HYDRO | Approved | 5th Floor 200 psi approved Building 1 is all done on OH PIPIING & HYDROST | |
12/30/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Overhead pressure test at 200 PSI for 200 hours approved 4th floor. The following areas need corrections: 1409 upright coverage living duct work blocking 1408 upright coverage entry duct blocking 1402 upright coverage back bedroom duct blocking |
|
12/19/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Overhead pressure test at 200 PSI for 2 hours done on the 3rd floor In the following rooms: Room 1311 correct upright coverage extended head above duct work Room 1308 Add upright by A/C unit. |
|
12/12/2011 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Overhead pressure test at 200 PSI for 2 hours approved for the following area: Building #1 all of the1st and 2nd floors Need to correct sprinkler coverage in the following areas: Rooms 1105 insulation and duct work blocking uprights 1102 insulation blocking uprights 1205 duct work blocking uprights 1201 duct blocking uprights 1202 duct work blocking and correct coverage by draft stop 1207 insulation blocking uprights 1208 lower flex duct for proper upright coverage 2nd floor elevator shaft add upright coverage in room next to it. |