Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
04/12/2012 FIRE SPKLR - FINAL Approved
03/28/2012 FIRE SPKLR - FINAL Denied Need proof that a Hydro pressure test was done on piping at 200 PSI for 2 hours.
Tested all pull stations - passed
Tested all smokes - passed
Tested matrix system - passed
System is ready to be approved only when the pressure test is passed on piping