Permit: T11BU01554

Parcel: 12108066A


Addresses:

6161 E FAIRMOUNT ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T11BU01554

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2012 FIRE SPKLR - FINAL Approved
07/23/2012 FIRE SPKLR - FINAL Partial Approval All closets have had sprinklers installed and laundry room corrected. Final will be given when the walk-in cooler is installed.
07/12/2012 FIRE SPKLR - FINAL Denied Add sprinkler coverage in closets, this is a full NFPA 13 design not 13R or 13D.
Correct sprinkler coverage in the laundry room this is a ordinary hazard and not a light hazard.