Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T11BU01554
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2012 | FIRE SPKLR - FINAL | Approved | ||
07/23/2012 | FIRE SPKLR - FINAL | Partial Approval | All closets have had sprinklers installed and laundry room corrected. Final will be given when the walk-in cooler is installed. | |
07/12/2012 | FIRE SPKLR - FINAL | Denied | Add sprinkler coverage in closets, this is a full NFPA 13 design not 13R or 13D. Correct sprinkler coverage in the laundry room this is a ordinary hazard and not a light hazard. |