Permit: T11BU01348

Parcel: 111020440

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
12/20/2011 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
12/12/2011 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE MISSING BOND BUSHING
2) SPLIT BOLT CANNOT HAVE 2 WIRES ON IT
3) 1 1/4" WIRES TO BE DERATED