Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T11BU01345
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2012 | FIRE SPKLR - FINAL | Approved | ||
07/26/2012 | FIRE SPKLR - FINAL | Partial Approval | Need fire pump test results Kazal did not send copy to TFD | |
07/17/2012 | FIRE SPKLR - FINAL | Partial Approval | Flows and tampers tested in stairwell: 1st fl 39.00 sec, 2nd fl 31 sec., 3rd fl 38 sec., 4th fl 34 sec., 5th fl 34 sec., 6th fl 42 sec. All tampers tested in fire pump room passed. Painted heads in the following room and areas: Room 101 Hallway closet Room 103 Kitchen closet Room 104 Bathroom Room 107 Hallway Room 305 Bedroom closet Room 504 Kitchen closet Room 509 Living room and Hallway closet Room 510 Hallway Room 517 Kitchen closet Room 526 Hallway closet Room 605 Bedroom closet Room 607 Bedroom Closet |
|
07/02/2012 | FIRE SPKLR - FINAL | Partial Approval | Fire pump test done waiting for pump results to be sent to the office. 6 auto's and 6 mans done Churn 60% 100% & 150 % done Jockey tested and set Need to water proof fire pump controller cabenit 1 1/2" hole was cut on top and not used. |