Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T11BU01273
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
10/17/2011 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
10/03/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE HOOD, DUCT AND FAN ARE OK TYPE I 2) RE-POSITION APPLIANCES TO FIT UNDER THE HOOD 3) THERE IS NOT MAKE UP AIR TO THE KITCHEN 4) MAKE UP AIR UNIT IS ON THE ROOF, BUT HAS BEEN DISCONNECTED 5) INTERLOCK MAKE UP AIR UNIT WITH EXHAUST FAN |