Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
Permit Number - T11BU01214
Inspection Description - FIRE SPKLR - UG, PIPING, HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/03/2012 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | ||
01/13/2012 | FIRE SPKLR - UG, PIPING, HYDRO | Not ready for Inspection | 1. OK TO BURRY MARKED ON PLANS AND DATED. | |
10/28/2011 | FIRE SPKLR - UG, PIPING, HYDRO | Partial Approval | Hydrostatic test of 300 feet from South side of West pavilion addition completed. | |
10/26/2011 | FIRE SPKLR - UG, PIPING, HYDRO | Not ready for Inspection | OK TO BURRY PIPE UNDER STREET | |
10/24/2011 | FIRE SPKLR - UG, PIPING, HYDRO | Not ready for Inspection | Courtesy Inspection: Two sections C900 (40 ft), 8 inch fire line. Runs East to West near street. Ok to cover. | |
10/21/2011 | FIRE SPKLR - UG, PIPING, HYDRO | Not ready for Inspection | 1. OK TO BURRY 200 FT | |
09/30/2011 | FIRE SPKLR - UG, PIPING, HYDRO | Not ready for Inspection | 1. OK TO BURRY STILL NEED PRESSURE TEST. SOUTHEAST TAP INTO EXISTING 50 FT OUT. | |
09/26/2011 | FIRE SPKLR - UG, PIPING, HYDRO | Not ready for Inspection | Courtesy site check. |