Permit: T11BU01175

Parcel: 14041063B


Addresses:

3201 E UNIVERSAL WY

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
02/08/2012 FIRE SPKLR - OH PIPING & HYDRO Approved Check coverage in open area blocked by wall middle.
01/18/2012 FIRE SPKLR - OH PIPING & HYDRO Approved 200 PSI FOR 2 HOURS
ADD SPRINKLER COVERAGE IN RISER ROOM
ADD UPRIGHT SPRINKLER COVERAGE IN THE OPEN OFFICE AREA HEAD BLOKED BY 2 X 12 WOOD.