Permit: T11BU01114

Parcel: 13705495A


Addresses:

1150 W DREXEL RD


Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Permit Number - T11BU01114

Inspection Description - FIRE - ALARM FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/23/2011 FIRE - ALARM FINAL Approved
12/01/2011 FIRE - ALARM FINAL Partial Approval 1. Repair or replace smoke duct detectors to give a clear green light on the fire alalrm control panel.
2. Add lock outs on all breakers to main fire alarm panel and nac's.
10/17/2011 FIRE - ALARM FINAL Partial Approval 1. Label all panels as to where breakers are located in building & make sure lock outs are on breakers.
2. Horns/ Strobes are to loud 110 decimals or 15 decimals above sounds in room at high operation.
3. Repair sounder to FACP
4. Repair or replace strobe/horn in room 100 and corridor 158 failed to work.
5. Date all batteries in NAC's and FACP
6. Repair tamper switches to outside post valves for sprinkler shut offs - failed to work.
7. Repair phone lines
8. Check each sounder base some have failed to report missing device.