Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T11BU01114
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/23/2011 | FIRE - ALARM FINAL | Approved | ||
12/01/2011 | FIRE - ALARM FINAL | Partial Approval | 1. Repair or replace smoke duct detectors to give a clear green light on the fire alalrm control panel. 2. Add lock outs on all breakers to main fire alarm panel and nac's. |
|
10/17/2011 | FIRE - ALARM FINAL | Partial Approval | 1. Label all panels as to where breakers are located in building & make sure lock outs are on breakers. 2. Horns/ Strobes are to loud 110 decimals or 15 decimals above sounds in room at high operation. 3. Repair sounder to FACP 4. Repair or replace strobe/horn in room 100 and corridor 158 failed to work. 5. Date all batteries in NAC's and FACP 6. Repair tamper switches to outside post valves for sprinkler shut offs - failed to work. 7. Repair phone lines 8. Check each sounder base some have failed to report missing device. |