Permit: T11BU01111

Parcel: 103090670


Addresses:

3850 N COMMERCE DR


Inspection Status: Denied

Inspection History: FIRE SPKLR - FINAL

Permit Number - T11BU01111

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
09/27/2011 FIRE SPKLR - FINAL Denied 1. Last annual fire sprinkler inspection 6/8/2011.
2. Last 5 year check valve test 1/18/2000
3. Missing escutcheons at various locations.
4. Calculation plate on top of spare head box, not on riser.
5. Could only locate 2 of 3 heads.