Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2012 | FIRE - ALARM FINAL | Approved | ||
| 01/23/2012 | FIRE - ALARM FINAL | Denied | Still need to do fire pump test Tested all tampers in fire pump room and stairwells Need to wire tamper switch to panel for stairwell #1 standpipe butterfly valve Tested all water flows in stairwell #2, flow switch failed on 2nd floor went off at 4 sec. min 30 sec to max 2 mins Need to wire tamper and flow switch in annex garage area |