Permit: T11BU00945

Parcel: 11619376A

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
02/21/2012 FIRE - ALARM FINAL Approved
01/23/2012 FIRE - ALARM FINAL Denied Still need to do fire pump test
Tested all tampers in fire pump room and stairwells
Need to wire tamper switch to panel for stairwell #1 standpipe butterfly valve
Tested all water flows in stairwell #2, flow switch failed on 2nd floor went off at 4 sec. min 30 sec to max 2 mins
Need to wire tamper and flow switch in annex garage area