Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2012 | FIRE SPKLR - FINAL | Approved | ||
| 02/01/2012 | FIRE SPKLR - FINAL | Denied | Heads blocked in parking garage lower level 3 paint caps on sprinkler in bathroom annex 3rd Floor correct sprinmkler coverage in bathroom closet mens room, |
|
| 01/18/2012 | FIRE SPKLR - FINAL | Denied | Fire pump test was done on the emergency power generator no house electrical hooked up. Only a pump run was made to get a pump curve from the pump company, still need to do a full test on the pump with all power supplies hooked up. |