Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - UG, PIPING, HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2011 | FIRE SPKLR - UG, PIPING, HYDRO | Approved | 200 psi test for 2 hours approved Make sure all piping from street to riser is buried at 36" depth, clean ditch out of all rocks and install clean fill around pipe. Still needs flushed |