Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/22/2011 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
| 07/12/2011 | FIRE - KITCHEN EXH HOOD FINAL | Not ready for Inspection | 1. AS-Builds required. A total of 16 360 F and 450 F links are not on plans. Salamander not shown on plans. 1 ADP flow point. 2. Ansal system must be tied into alarm. 3. Trip test passed. |