Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2011 | FIRE SPKLR - FINAL | Approved | ||
| 08/01/2011 | FIRE SPKLR - FINAL | Denied | 1. 4 sprinkler heads greater then 7 ft 6 in off wall in conference room (room > 800 sq ft). 2. 1 sprinkler head closer then 4 inches to wall. |