Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T11BU00767

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/08/2011 FIRE SPKLR - FINAL Approved
08/01/2011 FIRE SPKLR - FINAL Denied 1. 4 sprinkler heads greater then 7 ft 6 in off wall in conference room (room > 800 sq ft).
2. 1 sprinkler head closer then 4 inches to wall.