Permit: T11BU00649

Parcel: 11717023E


Addresses:

88 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T11BU00649

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2011 FIRE SPKLR - FINAL Approved
10/20/2011 FIRE SPKLR - FINAL Not ready for Inspection 1.PENTHOUSE ON ROOF HEAD TO CLOSE TO LIGHT.
2. 9TH FLOOR LEGAL ROOM WEST WALL HEAD TWO FAR FROM WALL.
3. 8TH FLOOR FAR EAST LINE PUT UPRIGHTS.
4. 8TH FLOOR NEAR ROOM 843 STRAIGHTEN PIPE.
5. 7TH FLOOR PLUG HEAD OVER STAIR 6. 2ND AND 4TH HEAD.
6. 6TH FLOOR NORTHSIDE STRAIGHTEN PIP OUSIDE OF ROOM 634.
7. CHECK 5TH FLOOR FILE ROOM 5C LOCKED.
8. 5TH FLOOR MECHANICAL ROOM TIGHTEN HEAD UNDER DUCT
9. 4TH FLOOR DOWN CHECK TO ASSURE ALL TAPE REMOVED FROM HEADS.
10. 4TH FLOOR STAIRWELL 6 PLUG THREE HEADS.
11. 3RD FLOOR HEAD TO FAR FROM WALL NEAR MECHANICAL ROOM 3.
12. 3RD FLOOR NEAR ELEVATOR WEST MOVE HEAD BACK
13. CENTRAL PLANT 3RD LINE SPIN TO UPRIGHT.
14. CENTRAL PLANT ADD JACKET SECOND LINE.
15. 2ND SOUTH AND THIRD SOUTH JACKET HEADS UNER DUCT.
16. AUDITORIUM ADD ONE HEAD IN CENTER ROOM.
17. 2ND FLOOR DEAD SPOT NEAR ROOM 285.
18. L1 SERVICE BAY HEAD OBSTRUCTED BY PIPE.
19. L1 SERVICE BAY ROLL PIPE NEAR ROLL UP DOOR.
20. L3 FAR EAST DROP HEAD ONE INCH BELOW DUCT
21. STILL NEED TAMPERS AND FLOW TESTED.
10/13/2011 FIRE SPKLR - FINAL Partial Approval PUMP TEST PASSED