Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T11BU00583
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2011 | FIRE SPKLR - FINAL | Approved | ||
07/21/2011 | FIRE SPKLR - FINAL | Denied | Sprinkler head in hallway installed wrong, sidewall sprinkler head can not be more than 4" away from wall. Head at this time is 9" from wall. FDC still not repaired hard to turn |
|
07/20/2011 | FIRE SPKLR - FINAL | Denied | Fix hangers for sprinkler piping in basement Replace gauges on riser Add sprinkler coverage in hallway Replace painted head southeast entry door Fix FDC hard to turn Need inspector test valve Replace painted signs on riser |
|
07/18/2011 | FIRE SPKLR - FINAL | Cancelled |