Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T11BU00583

Parcel: 12405226B


Addresses:

928 E 6TH ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T11BU00583

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/02/2011 FIRE SPKLR - FINAL Approved
07/21/2011 FIRE SPKLR - FINAL Denied Sprinkler head in hallway installed wrong, sidewall sprinkler head can not be more than 4" away from wall. Head at this time is 9" from wall.
FDC still not repaired hard to turn
07/20/2011 FIRE SPKLR - FINAL Denied Fix hangers for sprinkler piping in basement
Replace gauges on riser
Add sprinkler coverage in hallway
Replace painted head southeast entry door
Fix FDC hard to turn
Need inspector test valve
Replace painted signs on riser
07/18/2011 FIRE SPKLR - FINAL Cancelled