Permit: T11BU00385

Parcel: 117067030


Addresses:

345 E CONGRESS ST


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T11BU00385

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/18/2011 FIRE SPKLR - FINAL Approved
09/27/2011 FIRE SPKLR - FINAL Partial Approval Fire pump passed final test, still need the following:
1. Revisions will be required to the original permit to include details of the mechanical room. These include but are not limited to:
Details for walls ect.
Electrical including pump controls
Heat for pump room per NFPA 20
Drain for the pump room per NFPA 20
Model and serial numbers for jockey and fire pumps
2. Placement of all piping, valves normally open or closed.
3. All tampers and flows
4. Rewire plug for block heater, electrical cord to short.
5. Need copy of pump test (flows and table)
09/09/2011 FIRE SPKLR - FINAL Denied Pump test required.
09/07/2011 FIRE SPKLR - FINAL Cancelled IVRS - RI canceled