Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T11BU00368
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2011 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
06/09/2011 | FIRE SPKLR - OH PIPING & HYDRO | Denied | Still need to do 200 psi test Correct upright coverage by duct work x2 Correct upright coverage in kitchen area heads blocked by duct work. Add sprinkler coverage upright in folding door area. |