Permit: T11BU00364

Parcel: 13208007J


Addresses:

2499 E AJO WY


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T11BU00364

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/08/2011 FIRE SPKLR - FINAL Approved
05/26/2011 FIRE SPKLR - FINAL Partial Approval All deficiencies noted by Inspector Schultz corrected. OK to occupy. Final approval pending installation of Fire Department lock boxes on gates from 2329 E. Ajo, where the hydrant for this property is located. Also need sign on rolling gate on east side of 2329 E. Ajo stating that is the access to 2499 E. Ajo (also needs lock box).
05/19/2011 FIRE SPKLR - FINAL Partial Approval Correct sprinkler coverage in the following areas:
1. Dead end hallway upright coverage.
2. Work station area above office upright.
3. Painted upright above office/exam room by work station.
Get insulation off of sprinkler heads.