Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T11BU00364
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2011 | FIRE SPKLR - FINAL | Approved | ||
05/26/2011 | FIRE SPKLR - FINAL | Partial Approval | All deficiencies noted by Inspector Schultz corrected. OK to occupy. Final approval pending installation of Fire Department lock boxes on gates from 2329 E. Ajo, where the hydrant for this property is located. Also need sign on rolling gate on east side of 2329 E. Ajo stating that is the access to 2499 E. Ajo (also needs lock box). | |
05/19/2011 | FIRE SPKLR - FINAL | Partial Approval | Correct sprinkler coverage in the following areas: 1. Dead end hallway upright coverage. 2. Work station area above office upright. 3. Painted upright above office/exam room by work station. Get insulation off of sprinkler heads. |