Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T11BU00354
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/09/2011 | FIRE SPKLR - FINAL | Approved | ||
08/23/2011 | FIRE SPKLR - FINAL | Denied | Need as bults Heads still 16 feet apart at east end of hallway 1st floor |
|
08/18/2011 | FIRE SPKLR - FINAL | Denied | Alarm panel not functional. No flows or tampers tested. First floor - Head in electrical room too close to panel (need 4" minimum). Head in prep room is above refrigerators without 18" clearance (relocate). Head in southwest exit corridor 8' off wall (add head). Need escutcheon room 102. Heads at end of east end corridor 16' apart (add 1 or relocate). Heads in elevator shaft uprights in sidewall position. (replace with sidewalls). Need head wrench for head box. Second floor - last head in southwest corridor 8' off wall (add or relocate). Two heads in heads in water softener room are obstructed by lights. Lower deflectors. Need escutcheons in room 229 & 227. Fourth floor - All heads in storage room are too high, not 1" clear to deflector. Lower or rotate pipe and change to prendents. Second floor |
|
05/13/2011 | FIRE SPKLR - FINAL | Denied | 1. Need to check to see if side walls on forth floor are to close. Called tim with alan fire on 5/13/11 he stated he would call harvy on 5/16/11. |