Inspection History Details
Inspection Status: Partial Approval
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T11BU00182
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2011 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | 1. Trip test passed. 2. Electrical outlet behind fryer does not shut off when suppression systen is operated. 3. Need to verify Range Guard cylinder is correct size. |
|
04/22/2011 | FIRE - KITCHEN EXH HOOD FINAL | Not ready for Inspection | Not ready for inspection 4/22/11 |