Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2011 | FIRE SPKLR - OH PIPING & HYDRO | Approved | 200 psi test for 3 hours okay 1. Need as bults for page FP5 area under mezzanine 2. Add coverage under duct in hallway X 2 3. Add coverage 2nd floor mech. Room under duct 4. Add coverage 2nd floor room next to mech. room and 2 heads to far off wall 8' feet |