Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T11BU00165
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/08/2011 | FIRE SPKLR - FINAL | Approved | ||
11/15/2011 | FIRE SPKLR - FINAL | Denied | Still need separate permit for undergorund and 200 psi test and flush. | |
10/12/2011 | FIRE SPKLR - FINAL | Denied | 1. Fill hole around pipe in riser room 2. Correct coverage under stairs in lobby 3. Upstairs mech. Room add coverage under duct 4. 2nd floor room above riser room head 8' foot off wall to far 5. 2nd floor southeast room move head over 3" inches to far off wall |
|
04/06/2011 | FIRE SPKLR - FINAL | Not ready for Inspection | 1. CHECK REQUIRED SPRINKLER COVERAGE UNDERSTAIRS. 2. NEED TO ADD HEAD ARM OVER IN ROOM 207 MECHANICAL ROOM TO COMPENSATE FOR DUCT WORK. |