Permit: T11BU00022

Parcel: 107130490


Addresses:

2747 N STONE AV

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
03/02/2011 FIRE - KITCHEN EXH HOOD FINAL Approved Approved 3/2/11
02/24/2011 FIRE - KITCHEN EXH HOOD FINAL Denied Not Approved 2/24/11
1.) The appliances must be a minimum of 6 inches inside the hood canopy.
2.) The refrigerator under the hood must be relocated out from under or the power supplying it must be wired to shut off upon activation of the system.
3.) Must replace the filters. Mesh type filters are prohibited.
4.) All components tested and approved.
5.) OK for cooking operations.