Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
03/31/2011 FIRE SPKLR - OH PIPING & HYDRO Approved PER PH CALL
03/17/2011 FIRE SPKLR - OH PIPING & HYDRO Partial Approval rev
03/07/2011 FIRE SPKLR - OH PIPING & HYDRO Approved
02/28/2011 FIRE SPKLR - OH PIPING & HYDRO Partial Approval OH & piping pressure P/A. Required to complete test over canopy area (see plans).