Permit: T10PL01987

Parcel: 135057030


Addresses:

2166 S CALLE POLAR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/13/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
12/23/2010 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE ROOF JACKS AT ROOF PENETRATIONS
2) PROVIDE DBL WALL VENT PIPE FOR WATER HEATER MINIMUM 3' ABOVE EVAP COOLER
3) REMOVE COPPER FLEX FROM T & P DRAIN LINE
4) GAS FLEX CANNOT PASS THRU THE CABINET OF THE FURNACE
5) LEFT GAS CARD
6) NEED TO RETEST SYSTEM AFTER ROOF JACKS ARE INSTALLED
7) RECALL FOR FINAL INSPECTION