Permit: T10PL01968

Parcel: 106020810


Addresses:

271 E PASTIME RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/20/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
12/30/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) BLACK IRON PIPE MAY NOT BE INSTALLED IN OR ON THE GROUND, BUT MUST BE KEPT AT LEAST 6" ABOVE GRADE
2) PIPING BELOW GRADE SHALL BE SCOTCH COAT PIPE
3) FITTINGS AND PIPING MARRED BY WRENCHES, SHALL BE HALF OVER LAPPED, DBL WRAPPED WITH 10 MIL TAPE AND TAPE PRIMER
4) EXTEND T & P RELIEF DRAIN TO 6"-24" ABOVE GRADE
5) SINGLE WALL REQUIRES 6" CLEARANCE FROM COMBUSTIBLES