Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/06/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS MADE OK |
|
| 11/30/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) REQUIRE GAS BOND BETWEEN WATER AND GAS PIPING 2) THIS PERMIT IS FOR A GAS METER RELOCATE 3) INSPECTOR DID NOT ENTER HOUSE AS GAS IS ON AT THIS TIME. HOEVER, WATER HEATER HAS BEEN MOVED TO THE OUTSIDE AT SOME TIME, WITHOUT BENEFIT OF INSPECTION. SOME OF THE SAFETY VIOLATIONS INCLUDE: IMPROPER VENT MATERIAL, IMPROPER VENT TERMINATION, INCORRECT PAD AND I COULD NOT SEE T & P RELIEF DRAIN |