Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T10PL01765
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/22/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
11/19/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE PERM CAP FOR DOWNSTAIRS FURNACE VENT FROM OLD WATER HEATER VENT OR CORRECT VENT TRANSITION (S.W.) 2) PROVIDE CORRECT TRANSITION FOR UPSTAIRS FURNACE VENT (NORTH EAST) 3) CONTRACTOR ON SITE WILL MAKE CORRECTIONS 4) GAS CLEARANCE LEFT AT METER |
|
11/16/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) ALL VENTING FOR GAS APPLIANCES TO BE APPROVED MATERIALS, SECURED WITH APPROVED METHODS 2) ALL PIPING TO BE PROPERLY SUPPORTED AND SECURED AT CORRECT INTERVALS 3) TEST ALL PIPING TO DOWNSTREAM SHUT OFF VALVE (ROOF TOP UNIT AT NORTH WEST) 4) REMOVE ALL TAPE FROM VENT CONNECTORS PROVIDE FASTENERS RETEST AND CALL BACK |