Permit: T10PL01753

Parcel: 13308500A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T10PL01753

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/23/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
11/17/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) TEST TO HOLD FOR 15 MINUTES WITH NO LOSS OF PRESSURE
11/15/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE TEST GAUGE IN 1/10 INCREMENTS
2) TEST TO BE MINIMUM 10 PSI AT TIME OF INSPECTION
3) VALVES TO BE LISTED FOR GAS USE
4) PIPING TO BE SUPPORTED AND SEALED AT BLDG ENTRANCE AND AT CORRECT INTERVALS
5) ALL VENTING CONNECTIONS FOR FURNACES TO BE MADE UP COTRRECTLY, SECURED PROPERLY WITH FASTENERS
6) PROVIDE BONDING OF BLDG GAS SYSTEM
7) PROVIDE ACCESS TO ROOF FOR VENT TERMINATION
8) NO TAPE ON VENT CONNECTION