Permit: T10PL01709

Parcel: 10512024F


Addresses:

4040 N ORACLE RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/15/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
11/10/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) THE PLAN INCOMPLETE-IT SHOWS A 2" LINE FROM THE GENERATOR DIRECTLY TYING INTO THE METER. SHOW THE 2 INCH LINE TYING INTO THE EXISTING 2" LINE FEEDING THE TARGET STORE. INCLUDE TOTAL LOAD FROM STORE INTO THE LOAD DEMAND FROM THE GENERATOR
2) SEE 1211.10.1 2006 UPC-REQUIRES A VALVE UPSTREAM OF THE REGULATOR. ALSO GENERATOR REQUIRES A SHUT OFF VALVE WITHIN 6'
3) HOW IS THE PIPING UPSTREAM OF THE GAUGE TO BE TESTED ?