Permit: T10PL01706

Parcel: 135021970

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/16/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
11/08/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) TEST TO HOLD MINIMUM 10 PSI FOR 15 MINUTES WITH NO LOSS OF PRESSURE
11/05/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) MAKE CONNECTION INTO BLDG AND RETEST ENTIRE GAS SYSTEM
2) ALL TOOL MARKS, FITTINGS AND BLACK PIPE TO BE PRIMED WITH PIPE TAPE PRIMER THEN WRAPPED WITH PIPE TAPE TO 6" ABOVE GRADE