Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE SEE NOTES #2 AND 3 FROM 11/10/10 INSPECTION AND CALL IN BOTH PERMITS ON SAME DAY FOR INSPECTION NOTE: GAS FLEX CANNOT PASS THRU FURNACE APPLIANCE HOUSING, GAS PIPING TO BE ARRANGED ? EITHER APPLIACNE CAN BE REMOVED WITHOUT GAS PIPING DISASSEMBLY. TAPE IS NOT PERMITTED ON VENT CONNECTORS ONLY FASTENERS |
|
| 11/10/2010 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CORRECT SLOPE AND LEAK ON T & P 2) PROVIDE A PERMIT FOR NEW FURNACE 3) NOTE GAS IS UNDERSIZED FOR FURNACE |