Permit: T10PL01680

Parcel: 136283860

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/14/2010 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
11/08/2010 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) TEST FROM METER THRU TO HOUSE ONLY-OK TO COVER YARD
2) PROVIDE ALL CORRECTIONS LISTED AND RETEST SYSTEM
11/02/2010 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE MININUM 12" BURIAL DEPTH
2) PROVIDE PIPE TAPE PRIMER THEN PIPE TAPE ALL UNDERGROUND TOOL MARKS AND FITTINGS
3) UNION TO BE ABOVE GRADE IN ACCESSIBLE LOCATION
4) TEST TO BE 10 PSI MINIMUM HOLDING WITH NO LOSS OF PRESSURE FOR 15 MINUTES
5) PIPE IN DITCH TO REST ON FIRM BEDDING WITH NO STRAIN ON PIPING (STRAIGHT LINE)
6) PROVIDE WATER HEATER TEMPERATURE AND PRESSURE RELIEF DRAIN TO DAYLIGHT (GRAVITY)
7) INSTALL APPROVED GAS SHUT OFF VALVES FOR APPLIANCES
8) PIPING TO BE ARRANGED ON FURNACE/WATER HEATER AREA TO PROVIDE REMOVAL OF BOTH APPLIANCES WITHOUT DISASSEMBLY AND BE PROPERLY SECURED
9) PROVIDE BONDING OF BLDG GAS SYSTEM
10) VENT FROM WATER HEATER TO BE PROPERLY CONNECTED TO DRAFT HOOD
11) PROVIDE PIPE FLASHING THRU ROOF
12) WATER HEATER AND FURNACE VENT TO BE EXTENDED TO 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' WITH APPROVED DBL WALL VENT PIPING AND VENT CAP