Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T10PL01656
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2010 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
12/07/2010 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) 1 1/2" TOWARDS POOL OK NEED TO SEE CONNECTION AND BACKFLOW CERTS 2) 3' EAST AND NORTH RUNS WITH 140 PSI AND STERILIZATION IN PROGRESS 3) LEAVE FINAL CONNECTION OPEN FOR INSPECTION |
|
11/30/2010 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) EAST SIDE WITH 150 PSI 2) MIN 50 PPM FOR STERILIZATION |
|
11/24/2010 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) ENTIRE WEST LOOP TO BLANTON WITH 100 + PSI HYDORSLATE TEST 2) OK TO COVER WITH CLEANFILL AS REQUIRED |
|
11/12/2010 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) PROVIDE APPROVED PLANS 2) 3" MAIN FROM RP LOCATION TO 4223 OK TO COVER 3) PLAN (DIAGRAM) INDICATES BRANCHES TO BE REPLACED 4) UPC 609.3 REQUIRES STERILIZATION OF DOMESTIC WATER PIPING PRIOR TO USE 5) THIS IS PHASE II |