Permit: T10PL01656

Parcel: 99999999A


Addresses:

4230 E ALLISON RD


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T10PL01656

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2010 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
12/07/2010 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) 1 1/2" TOWARDS POOL OK NEED TO SEE CONNECTION AND BACKFLOW CERTS
2) 3' EAST AND NORTH RUNS WITH 140 PSI AND STERILIZATION IN PROGRESS
3) LEAVE FINAL CONNECTION OPEN FOR INSPECTION
11/30/2010 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) EAST SIDE WITH 150 PSI
2) MIN 50 PPM FOR STERILIZATION
11/24/2010 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) ENTIRE WEST LOOP TO BLANTON WITH 100 + PSI HYDORSLATE TEST
2) OK TO COVER WITH CLEANFILL AS REQUIRED
11/12/2010 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) PROVIDE APPROVED PLANS
2) 3" MAIN FROM RP LOCATION TO 4223 OK TO COVER
3) PLAN (DIAGRAM) INDICATES BRANCHES TO BE REPLACED
4) UPC 609.3 REQUIRES STERILIZATION OF DOMESTIC WATER PIPING PRIOR TO USE
5) THIS IS PHASE II