Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 10/28/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ANSWER 2) PROVIDE TEST REPORT FROM A CERTIFIED BACK FLOW ASSEMBLY TESTER 3) INSTALL THE UNION REQUIRED BY CODE FOR SERVICING THIS WATER SUPPLIED EQUIPMENT 4) CORRECT LEAK AS PREVIOUSLY NOTED 5) CONTINUED NOT READY'S WILL RESULT IN A REINSPECTION FEES 4) |
|
| 10/12/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE INSTALLATION INSTRUCTIONS AND OR LISTING FOR WATTS 800M4QT PRESSURE VACUUM BREAKER INSTALLED IN OTHER THAN UPRIGHT POSITION 2) REPAIR LEAK AT UNDERGROUND LOCATION DOWNSTREAM 3) PROVIDE CERTIFICATION FOR BACKFLOW DEVICE |
|
| 10/08/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE CORRECT BACKFLOW PROTECTION FOR VALVES DOWN STREAM OF ATMOSPHERIC VACCUM BREAKER |