Permit: T10PL01449

Parcel: 115020390


Addresses:

524 E WAVERLY ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/22/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS MADE OK
2) OK FOR GAS
3) UCC LEFT AT METER
09/20/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) ROOF TOP PIPING NOT SUPPORTED PROPERLY
2) PIPING AT OLD METER LOCATION NOT SUPPORTED
3) THREAD PROTECTORS ARE NOT PERMITTED IN LIEU OF COUPLINGS
4) NO APPROVED CLEARANCES AT WATER HEATER VENT
5) WATER HEATER REQUIRES AN APPROVED SHUT OFF VALVE
6) FLEX CONNECTOR AT FURNACE MAY NOT PASS THRU A WALL, PARTITION OR APPLIANCE HOUSING
7) PRESSURE GAUGE NOT OPERATING PROPERLY