Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS MADE OK 2) OK FOR GAS |
|
| 09/15/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 09/14/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PIPING TO BE 18" MINIMUM DEPTH 2) TEST TO BE ON ENTIRE SYSTEM 3) SUPPORT ALL PIPING 4) PROVIDE MINIMUM 40 MIL THICKNESS OF PIPE WRAP ON ALL UNDERGROUND TOOL MARKS AND FITTINGS 5) PROVIDE MINIMUM 3' ABOVE COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE FOR WATER HEATER VENT TERMINATION WITH APPROVED VENT PIPING AND CAP |