Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2010 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS MADE OK 2) OK FOR GAS |
|
| 09/01/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SEE NOTE #1 FROM 8/24/10 GAUGE TO BE 15 POUND GAUGE IN 1/10 POUND INCREMINTATION 2) SEE NOTE #2 FROM 9/24/10-EXPOSE ALL NEW WORK INCLUDING POINT OF CONNECTION TO EXISTING 3) SEE NOTE #5 FROM 08/24/10-PROVIDE INSPECTION HISTORY FOR NEW ROOF TOP UNIT |
|
| 08/31/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ALL OF LIST FROM 8/24/10 BEFORE CALLING FOR INSPECTION |
|
| 08/24/2010 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) REQUIRE A TEN POUND TEST ON GAS SYSTEM 2) EXPOSE ALL NEW PIPING FOR INSPECTION NOTE: BLACK IRON PIPE NOT APPROVED BELOW GRADE 3) FURNACE HAS BEEN REMOVED 4) CAP OFF ALL OPEN PIPING OR REINSTALL FURNACE 5) PROVIDE PERMIT FOR NEW ROOF TOP UNIT |