Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2010 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 08/24/2010 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* NOTES FOR BOTH ADDRESSES: 1) 4651 TEST OK, PROVIDE TEST FOR 4649 2) BOTH UNITS TO HAVE CORRECT VENTING OF APPLIANCES WITH APPROVED MATERIALS |
|
| 08/23/2010 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* NOTES FOR BOTH ADDRESSES: 1) TEST TO BE 10 PSI MINIMUM AND HOLDING FOR 15 MINUTES WITH NO LOSS OF PRESSURE 2) ALL TOOL MARKS, FITTINGS TO BE PRIMED AND TAPED TO ACHIEVE 40 MIL WRAP 3) PROVIDE WEATHER SEAL AT ROOF ALL PIPING PENETRATIONS 4) PROVIDE BONDING OF BLDG GAS PIPING 5) ALL APPLIANCE VENTING TO BE INSTALLED CORRECTLY WITH APPROVED VENTING MATERIALS TERMINATING 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF INTAKE WITH APPROVED VENT CAP 6) ALL T & P RELIEFS TO GRAVITY DRAIN TO DAYLIGHT 7) SECURE ALL PIPING AND PROVIDE PROTECTION PLATES 8) CAP OR REMOVE OLD GAS PIPING |