Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2010 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) CORRECTIONS MADE OK 2) OK FOR GAS |
|
| 09/14/2010 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) TEST TO HOLD WITH NO LOSS OF PRESSURE 2) VENT FROM WATER HEATER TO BE CONNECTED PROPERLY TO DRAFT HOOD AND SECURED TO INNER LINGER OF DBL WALL VENT PIPE. PROVIDE FASTENERS AT ALL JOINTS OF SINGLE WALL PIPING 3) T & P DRAIN TO GRAVITY DRAIN TO DAYLIGHT 4) PROVIDE COMBUSTION AIR FOR 35,00 BTU DEVICE 5) PROVIDE BONDING OF BLDG GAS PIPING 6) PROVIDE FIRM BEDDING FOR PIPING IN DITCH 7) PROVIDE APPROVED GAS VALVES AT APPLIANCES 8) FLEX CANNOT BE USED AS PIPING AT FURNACE. SUPPORT FURNACE PIPING |
|
| 08/19/2010 | PLUMBING - GAS PRESSURE TEST | Cancelled | CANCELLED PER HOMEOWNER PEDRO #240-7936 | |
| 08/19/2010 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* |