Permit: T10PL01202

Parcel: 133222490


Addresses:

510 N BAHAMAS DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/31/2018 PLUMBING - FINAL Approved
05/24/2018 PLUMBING - FINAL Denied TP VALVE NEEDS TO BE PLUMBED CORRECTLY AND WATER HEATER NEEDS CATCH PAN
08/03/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) RISER CORRECTION OK
2) COURTESY UNSCHEDULED INSPECTION AND CLEARANCE PROVIDED PER LEE RAY ACTING AS BLDG OFFICIAL
08/02/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) WATER HEATER INSTALLED WITHOUT PERMITS
2) REQUIRES APPROVED T & P PIPING WITH TERMINATION INTO PAN WITH PETITION OF APPEAL FORM
3) TEST T & P FOR PROPER OPERATION
4) GAS FLEX MAY NOT BE REUSED
5) SEDIMENT TRAPS ARE REQUIRED AT WATER HEATER AND FURNACE GAS SUPPLY
6) ELECTRICAL BONDING IS REQUIRED AT METER; EXTEND GAS RISER PRIME AND WRAP ALL TOOL MARKS BELOW GRADE
7) INSTALL PROPERLY SIZED AND APPROVED FOR GAS PIPING CLAMPS
8) WAS A PERMIT OBTAINED FOR NEW MECHANICAL UNIT ?