| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/23/2010 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE BACKFLOW PROTECTION ON IRRIGATION SUPPLY-HEALTH HAZARD 2) HAMMER ARRESTORS REQUIRED AT WB 3) 18" OF METALIC PIPING REQUIRED PAST SWEAT CONNECTIONS AT WATER HEATER 4) REMOVE PLUMBERS TAPE AND PROVIDE PLASTIC 5) ISOLATION CLAMPS LISTED FOR USE WITH PEX 6) COPPER 2 HOLE CLAMPS ARE NOT APPROVED FOR PLASTIC 7) SEAL ABANDONED PIPES IN FLOOR 8) SECURE TUBING UNDER SINK WITH ISOLATION FROM SAFETY ? 9) INSULATE PIPES TOUCHING ROOF FOR FREEZER PROTECTION |